文章来源:http://www.trcables.com/ 作者:上海嗨润 发布时间::2018-01-18 14:03 浏览次数:次
APPLICATION
This cables are designed specifi cally to suit the broad spectrum of requirements of Variable Speed
Drives and also include features for reducing the transmission of electromagnetic interference.
This range of screened cables drastically reduce interferences from electrical noise, especially in
Variable Speed Drive (VSD) applications and are manufactured with fixed conductors.
With shield conductivity of 1/10th of phase conductor conductivity, this range of VSD cables
effectively restrain radiated and conducted radio-frequency emissions.
STANDARDS
Basic design adapted to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE |
Reduced Fire Propagation |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner sheath1: PVC Compound
Screen: Copper TapeInner sheath2: PVC Compound
Armouring: Galvanised Steel Wire
Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance,
anti rodent and anti termite properties can be offered as option. Compliance to fire performance
standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the
PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour as per BS7671
|
With Earth Conductor |
Without Earth Conductor |
2Cores |
- |
Brown, Blue |
3Cores |
Yellow/Green, Brown, Blue |
Brown, Gray, Black |
4Cores |
Yellow/Green, Brown, Gray, Black |
Brown, Gray, Black, Blue |
5Cores |
Yellow/Green, Brown, Gray, Black, Blue |
Brown, Gray, Black, Blue, Black |
Above 5 Cores |
Yellow/Green, Black Numbered |
Black Numbered |
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5secs max.
Minimum bending radius: 12 x Overall Diameter (for 1.5mm2 to 300mm2)
CONSTRUCTION PARAMETERS
Conductor | FGD400 1RCVMV-R | |||||||
No. of Core |
No./ |
Nominal |
Nominal |
Diameter |
Diameter |
Armour |
Nominal |
Approx. |
mm2 |
No./mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
4x1.5 |
7/0.53 |
0.7 |
1.8 |
9.7 |
12.1 |
13.9 |
17.7 |
640 |
4x2.5 |
7/0.67 |
0.7 |
1.8 |
10.7 |
13.1 |
14.9 |
18.7 |
730 |
4x4 |
7/0.85 |
0.7 |
1.8 |
12.0 |
14.4 |
16.2 |
20.0 |
870 |
4x6 |
7/1.04 |
0.7 |
1.8 |
13.4 |
15.8 |
18.3 |
22.1 |
1180 |
4x10 |
7/1.35 |
0.7 |
1.8 |
15.6 |
18.0 |
20.5 |
24.3 |
1490 |
4x16 |
7/1.70 |
0.7 |
1.8 |
18.1 |
20.5 |
23.7 |
27.5 |
2070 |
4x25 |
7/2.14 |
0.9 |
1.8 |
22.3 |
24.1 |
27.3 |
31.1 |
2790 |
4x35(S) |
7/2.52 |
0.9 |
1.8 |
25.0 |
26.8 |
30.0 |
33.8 |
2940 |
4x50(S) |
19/1.78 |
1.0 |
2.0 |
27.8 |
29.6 |
32.8 |
37.0 |
3500 |
4x70(S) |
19/2.14 |
1.1 |
2.2 |
31.6 |
33.4 |
37.4 |
42.0 |
5000 |
4x95(S) |
19/2.52 |
1.1 |
2.3 |
35.4 |
37.2 |
41.2 |
46.0 |
6300 |
4x120(S) |
37/2.03 |
1.2 |
2.5 |
39.0 |
40.8 |
45.8 |
51.0 |
8200 |
4x150(S) |
37/2.25 |
1.4 |
2.6 |
42.0 |
43.8 |
48.8 |
54.2 |
9600 |
4x185(S) |
37/2.52 |
1.6 |
2.8 |
47.8 |
49.6 |
54.6 |
60.4 |
11500 |
4x240(S) |
61/2.25 |
1.7 |
3.0 |
54.0 |
55.8 |
60.8 |
67.0 |
14400 |
4x300(S) |
61/2.52 |
1.8 |
3.0 |
58.0 |
59.8 |
64.8 |
71.4 |
17200 |
Electrical Properties
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor crosssectional area |
Reference Method 1 (clipped direct) |
Reference Method 11 (on a perforated horizontal cable trayor Reference Method 13 [free air] ) |
In single-way ducts |
Laid direct in ground | ||||
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
27 |
23 |
29 |
25 |
- |
23 |
- |
28 |
2.5 |
36 |
31 |
39 |
33 |
- |
30 |
- |
36 |
4 |
49 |
42 |
52 |
44 |
- |
40 |
- |
48 |
6 |
62 |
53 |
66 |
56 |
- |
50 |
- |
60 |
10 |
85 |
73 |
90 |
78 |
- |
65 |
- |
80 |
16 |
110 |
94 |
115 |
99 |
115 |
94 |
140 |
115 |
25 |
146 |
124 |
152 |
131 |
145 |
125 |
180 |
150 |
35 |
180 |
154 |
188 |
162 |
175 |
150 |
215 |
180 |
50 |
219 |
187 |
228 |
197 |
210 |
175 |
255 |
215 |
70 |
279 |
238 |
291 |
251 |
260 |
215 |
315 |
265 |
95 |
338 |
289 |
354 |
304 |
310 |
260 |
380 |
315 |
120 |
392 |
335 |
410 |
353 |
355 |
300 |
430 |
360 |
150 |
451 |
386 |
472 |
406 |
400 |
335 |
480 |
405 |
185 |
515 |
441 |
539 |
463 |
455 |
380 |
540 |
460 |
240 |
607 |
520 |
636 |
546 |
520 |
440 |
630 |
530 |
300 |
698 |
599 |
732 |
628 |
590 |
495 |
700 |
590 |
Voltage Drop (Per Amp Per Meter)
Conductor cross- sectional area |
2-core cable d.c. |
2 cables, single-phase a.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single-phase a.c. |
3 or 4 cables, |
||||
In ducts or in ground |
In ducts or in ground |
||||||||
1 |
2 |
3 |
4 |
5 |
6 |
||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
||||
1.5 |
31.0 |
31.0 |
27.0 |
31.0 |
25.0 |